Technical specifications
6.1 General technical data
Power Module PM330
86
Hardware Installation Manual, 12/2018, A5E32844552B AF
Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 6-2
Load cycles, Low Overload" and "High Overload"
Note
Please note the base load (100
% power or
current) for Low Overload is higher than the
base load for High Overload.
The load characteristics shown in the diagram are only examples. We recommend the use of
the "SIZER" engineering software to select the appropriate Power Modules based on the
load situation. See Configuring support (Page 116).
Definitions
•
LO base-load input current
100
% of the permissible input current with a
load cycle according to Low Overload.
•
LO base-load output current
100
% of the permissible output current with a
load cycle according to Low Overload.
•
LO base-load power
Power with LO base-load output current
•
HO base-load input current
100
% of the permissible in
put current with a
load cycle according to High Overload.
•
HO base-load output current
100
% of the permissible output current with a
load cycle according to High Overload.
•
HO base-load power
Power with HO base-load output current
•
Rated current I
N
Continuous current at the type rating, overload
not possible
Содержание PM330
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Power Module PM330 6 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 20: ...Introduction Power Module PM330 18 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 146: ...Appendix A 6 Abbreviations Power Module PM330 144 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 149: ......
Страница 150: ......