Technical specifications
6.1 General technical data
Power Module PM330
82
Hardware Installation Manual, 12/2018, A5E32844552B AF
6.1
General technical data
Table 6- 1
General technical data
Electrical data
Line system configurations
Grounded TN/TT systems or ungrounded IT systems (a grounded phase conductor is not
permissible in 690 V line supplies)
Line requirement
A line reactor (2% u
k
) must be connected in series
Line voltage
380 V (-
10 %)
...
480 V (+10 %)
500 V (-
10 %)
... 69
0 V (+10 %)
Line frequency
47 … 63 Hz
Output frequency
0 ... 150 Hz
(selecting an output frequency greater than 100 Hz works from SINAMICS firmware V4.7
SP6 HF3 and higher)
Displacement factor cos φ
power factor λ
0.96
0.75 ... 0.93 (with line reactor u
k
= 2%)
Inverter efficiency
> 98%
Short-circuit current rating
according to IEC, in conjunc-
tion with the specified fuses
160 ... 630 kW: 100 kA
Short-circuit current rating
according to UL61800-5-1
(up to 480 V AC or 600 V
AC), in conjunction with the
specified fuses
160 ... 630 kW: 100 kA
Can be used on line supplies that cannot supply more than 100 kA symmetrically at a max-
imum voltage of 480 V AC or 600 V AC when they are protected with the semiconductor
fuses specified in Chapter "Technical Data" of this manual.
Overvoltage category
III according to EN 61800-5-1
Electromagnetic compatibility
(EMC)
Emitted interference
•
Standard
•
with line filter
•
Category C3 (second environment) according to EN 61800-3
1)
•
Category C2 (first
*)
and second environments) according to EN 61800-3
*)
When used in the first environment, an appropriately trained and authorized technical
person must set up the drive and commission it.
NOTE: An appropriately trained and authorized technician is person or organization with
the required experience for setting up and/or for commissioning the drive systems, including
the associated EMC aspects.
Immunity
Use in the first and second environment according to EN 61800-3
Mechanical data
Degree of protection
IP20
Protection class
according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Cooling method
Forced air cooling AF according to EN 60146
Sound pressure level
L
PA
(1 m)
≤ 74 dB(A)
2)
Touch protection
according to EN 61800-5-1: For the intended purpose
Содержание PM330
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Power Module PM330 6 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 20: ...Introduction Power Module PM330 18 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 146: ...Appendix A 6 Abbreviations Power Module PM330 144 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 149: ......
Страница 150: ......