Technical specifications
6.2 Specific technical data
Power Module PM330
92
Hardware Installation Manual, 12/2018, A5E32844552B AF
Table 6- 4
PM330, frame size JX, 3-phase 380 … 480 VAC
Article No.
6SL3310-
1PE38-4AA0
1PE38-8AA0
1PE41-0AA0
Rated input current
- at 380/400 V, 45° C
- at 480 V, 45° C
- at 380/400 V, 55° C
- at 480 V, 55° C
870 A
702 A
740 A
596 A
945 A
767 A
803 A
652 A
1061 A
880 A
901 A
748 A
Rated input current DCP/DCN
(for 2/3 of the inverter power)
- at 510 V
DC
, 45 °C
- at 650 V
DC
, 45 °C
- at 510 V
DC
, 55 °C
- at 650 V
DC
, 55 °C
715 A
577 A
608 A
490 A
775 A
629 A
659 A
535 A
870 A
722 A
739 A
613 A
Rated output current I
N
- at 380/400 V, 45° C
- at 480 V, 45° C
- at 380/400 V, 55° C
- at 480 V, 55° C
840 A
677 A
714 A
576 A
910 A
739 A
774 A
628 A
1021 A
847 A
868 A
720 A
LO base load power
LO base load input current at 400 V
LO base load output current at 400 V
450 kW
850 A
820 A
500 kW
925 A
890 A
560 kW
1039 A
1000 A
HO base load power
HO base load input current at 400 V
HO base load output current at 400 V
355 kW
696 A
672 A
400 kW
756 A
728 A
450 kW
816 A
786 A
Fuse according to IEC
manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
2 x 3NE1334-2 //
(2 x 500 A / 690 V)
Siemens AG
≤ 100 kA
> 10.4 kA
2 x 3NE1435-2 //
(2 x 560 A / 690 V)
Siemens AG
≤ 100 kA
> 14.0 kA
2 x 3NE1436-2 //
(2 x 630 A / 690 V)
Siemens AG
≤ 100 kA
> 16.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Minimum line short-circuit current required I
kmin
1)
3NB3350-1KK26
(1000 A/690 V)
Siemens AG
8.6 kA
3NB3351-1KK26
(1100 A/690 V)
Siemens AG
17.0 kA
3NB3352-1KK26
(1250 A/690 V)
Siemens AG
18.0 kA
max. power loss, at I
N
, 45 °C, 400 V
10.418 kW
10.885 kW
12.495 kW
Required cooling air flow
450 l/s
450 l/s
450 l/s
Maximum connectable cross-section of the power
cable
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
Maximum connectable cross-section of the motor
cable
4 x 240 mm
2
4 x 500 kcmil
8 x 240 mm
2
8 x 500 kcmil
8 x 240 mm
2
8 x 500 kcmil
Maximum connectable cross-section of the DC link
cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 380 V/400 V
- line cable
- motor cable
3)
4 x 185 mm
2
4 x 150 mm²
4 x 185 mm
2
4 x 185 mm²
4 x 240 mm
2
4 x 240 mm²
Recommended cable cross-section for 480 V
- line cable
- motor cable
3)
4 x 120 mm
2
4 x 120 mm²
4 x 150 mm
2
4 x 150 mm²
4 x 185 mm
2
4 x 150 mm²
Recommended cable cross-section for 380 V/400 V
- DC link infeed (2/3 inverter power)
- Braking Module
4)
4 x 120 mm
2
35 mm²
4 x 150 mm
2
35 mm²
4 x 185 mm
2
35 mm²
Содержание PM330
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Power Module PM330 6 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 20: ...Introduction Power Module PM330 18 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 146: ...Appendix A 6 Abbreviations Power Module PM330 144 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 149: ......
Страница 150: ......