Connection
6.1 Electrical connection
WOGeneric TEAAC / 2008
28
Siemens AG Operating Instructions 1.03 1RQ671...-Z
Components provided by customer
You, the customer, provide the following components:
● Cable lug and component parts
● Cable glands
● Cable
● Parts for connection to equipment already on-site
Table 6-5
Parts for connection to equipment already on-site
Part number
Description
22.92.1
Hexagon bolt ISO 4017-M12x50-8.8
22.92.2
Hexagon bolt ISO 4017 M16X50-8.8
22.92.3
Washer ISO 7089-12-200HV-A2
22.92.4
Washer ISO 7089-16-200HV-A2
22.92.5
Washer ISO 7093-1-12-200HV-A2
22.92.6
Washer ISO 7093-1-16-200HV-A2
22.92.7
Conical spring washer DIN 6796-12-FST-MECH.ZN12C
22.92.8
Conical spring washer DIN 6796-16-FST-MECH.ZN12C
22.92.9
Spring washer DIN 128-A12-FST-A3L
22.92.10
Spring washer DIN 128-A16-FST-A3L
22.92.11
Hexagonal nut ISO 4032-M12-8.8
22.92.12
Hexagonal nut ISO 4032-M16-8
Selecting the cables
● When choosing connecting cables, you must take into account the rated current, possibly
the service factor, and the plant-specific conditions (e.g.ambient temperature, routing
type, etc. to IEC/EN 60204-1).
Connecting using cable lugs
Connection with cable lugs is only permitted for conductor cross-sections ≥ 70 mm
2
to
300mm², to prevent the cable lugs twisting on connection.
● Select the cable lugs according to the required cable cross-section and screw size.
Table 6-6
Technical specifications for selecting the cable lug
IEC
NEMA
Screw size
M16
M12
Max. cable cross section and max. number per
phase
6 x 300 mm
2
AWG 600 kcmil
Max. size of the cable lug
DIN 46235 16-300
Burndy YA36 2N
Содержание H-compact PLUS
Страница 2: ...24 06 2009 15 03 ...
Страница 10: ......
Страница 18: ......
Страница 22: ......
Страница 40: ......
Страница 60: ......
Страница 77: ......
Страница 80: ......
Страница 81: ......
Страница 83: ...Generic TEAAC 000010 001 en US Generic TEAAC 00001001EN05 ...