4BMounting / Installation
49BDetector lines
5
98 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
5.19
Detector lines
General cabling information
●
Preferably, twisted and non-shielded cables should be used. This also applies
to connecting the external alarm indicators.
●
Shielded cables are only required in special cases, such as strong high-
frequency fields.
See also
5.19.1
Connection diagram for FDnet detector line
The following applies to FDnet detector lines:
●
Loops, stubs and T-branches are possible.
●
You may only connect external alarm indicators to one detector.
●
Permissible cables for detectors with more than one external alarm indicator in
the collective, AnalogPLUS, and SIGMALOOP connection diagrams may be
migrated to the FDnet without any changes.
●
Note document 001508 for installation (calculation of the capacity layer).
See also
5.19.1.1
Use of unshielded cables
The connection is established from base to base using twisted or non-twisted wire
pairs.
Connection diagram for addressed detector line with and without external alarm indicators (without
shielded cables)
1 Control panel
3 Auxiliary terminals DBZ1190-xx
2 Detector bases FDB221/FDB221-AA, FDB222
4 External alarm indicator
+
-
+
-
+
-
+
-
+
-
+
-
LINE
+
-
+
-
+
-
+
-
+
-
+
-
+
-
-
+
+
-
+
-
+
-
1
2
3
4
2
+
4
+