7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
120 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
8.1.2
Detector lines
FDnet
Detector line
Operating voltage (modulated)
DC 12…33 V
Operating current (quiescent)
190…230
μA
Maximum current connection factor
1
Quiescent current connection factor
1
Address connection factor
1
Separator connector factor
1
Protocol
FDnet
Compatibility
See 'List of compatibility'
FDOOT241-Ax line separator
Line voltage:
●
Nominal
DC 32 V (= V
nom
)
●
Minimum
DC 12 V (= V
min
)
●
Maximum
DC 33 V (= V
max
)
Voltage at which the line separator opens:
●
Minimum
DC 7.5 V (= V
SO min
)
●
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches are closed
Max. 1.5 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 2 A (= I
S max
)
Leakage current when switches are open
Max. 1 mA (= I
L max
)
Serial impedance when switches are closed
Max. 0.4
Ω (= Z
C max
)
The line separator is closed via an actuation signal from the control panel. Required line voltage: DC 12…33 V (normal range)
FDOOT221 and FDOOT241-x
line separator
Line voltage:
●
Nominal
DC 32 V (= V
nom
)
●
Minimum
DC 12 V (= V
min
)
●
Maximum
DC 33 V (= V
max
)
Voltage at which the line separator opens:
●
Minimum
DC 7.5 V (= V
SO min
)
●
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches are closed
Max. 0.5 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 1 A (= I
S max
)
Leakage current when switches are open
Max. 1 mA (= I
L max
)
Serial impedance when switches are closed
Max. 0.4
Ω (= Z
C max
)
The line separator is closed via an actuation signal from the control panel. Required line voltage: DC 12…33 V (normal range)