3BPlanning
25BParameter sets: Neural fire detector
4
60 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
4.3.1.3
Specification
The table below shows the characteristics and fields of application of the
parameter sets of the neural fire detectors FDOOT241-x/-Ax
No.
Name
Optical
Thermal
Typ. Response
time
from - typ. - to
Sensitivity,
open fire
Sensitivity,
smoldering fire
Static activation
temperature
Differential
activation
temperature
4
Differential
activation
possible from
ambient
temperature:
[s]
[%/m]
[%/m]
[°C]
∆
T
[K]
[°C]
8
High Suppression
(from ES
≥30)
3
60 - 80 - 360
2.3
8
80
25
30
5
Suppression
90 -160 - 760
3.2
11.4
80
29
30
7
High Compensation
80
3.2
11.4
80
29
30
0
1
High Compensation
(only FDnet mode)
80
3.2
11.4
80
29
30
0
1
High Compensation
(only collective mode
from ES
≥13)
80
3.2
11.4
80
29
30
2
Robust
80
3.2
11.4
80
29
30
0
1
Insensitive
(only collective mode
up to ES <13)
30
3.2
11.4
80
29
30
4
Balanced
40 - 64 - 300
2.3
8
80
25
30
0
1
Sensitive
(only MS8 mode)
30
1.6
5.6
80
22
30
6
2
Fast Response
20 - 30
1.6
5.6
80
22
3
9
High Sensitive Fast
(from ES
≥30)
20 - 30
0.8
2.8
60
16
3
11
Super Sensitive
(from ES
≥50)
12
1.0
1.5
60
8
3
12
Universal Fast
(only in AnalogPLUS
mode)
8
2.3
8
80
25
30
14
Application-specific parameter sets
15
1
Delivery status; can only be selected in collective mode and MS8 mode.
2
Default status in AnalogPLUS mode as DOT1131A replacement.
3
Note chapter '
', 'High Suppression (8)' paragraph.
4
Applicable with fast temperature increases >10 K/min.
All parameter sets except for 8, 14, and 15 comply with standards EN 54-7 and
CEA 4021.