7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
124 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Collective maximum current connection factor/alarm verification
(FDOOT241-A9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Use as
Parameter set no. Parameter set name
Maximum
current
connection
factor
1
Alarm verification permitted on
control panel
Neural fire detector (FDOOT)
0
High Compensation
1
2
Yes
2
Robust
1.25
Yes
4
Balanced
1.25
Yes
5
Suppression
1.25
Yes
6
Fast Response
1.25
Yes
7
High Compensation
1
2
Yes
8
High Suppression
1.25
Yes
9
High Sensitive Fast
1.25
Yes
11
Super Sensitive
1.25
Yes
Wide-spectrum smoke detector
(FDO)
0
Universal
1.25
Yes
1
Universal
1.25
Yes
2
Robust
1.25
Yes
3
Sensitive
1.25
Yes
5
Super Sensitive
1.25
Yes
6
Ultra Sensitive
1.25
Yes
Heat detector (FDT)
0…4
All parameter sets
1.25
Yes
1
The maximum current connection factor of 1.5 applies to CS1115.
2
The maximum current connection factor of 1.25 applies to SIGMASYS SMG-S and SPF3500.