3BPlanning
28BDefault settings
4
69 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
4.5.2.2
Specifications
No. Name
Operating
temperature
typ. / max.
Static activation
temperature
1
Differential activation
temperature
2
Differential activation possible
from ambient temperature:
[°C]
[°C]
∆
T
[K]
[°C]
1
A1R
60 °C rate of rise
25 / 50
60
25
3
2
BR
80 °C rate of rise
40 / 65
80
29
30
1
Applicable with slow temperature increases <1 K/min.
2
Applicable with fast temperature increases of >10 K/min. When there is a slow temperature
increase of <10 K/min, this value rises by a few degrees.
All parameter sets meet the criteria of standard EN 54-5.
4.6
Default settings
The detector operates in the default parameter set as long as the control panel has
not assigned a valid parameter set to the detector.
The following table shows the default parameter set of the various fire detectors.
Fire detector
Default parameter set
FDOOT241-x/-Ax in FDnet mode
High Compensation
FDOOT241-9 in collective mode:
●
Sensor mode 0 (neural fire detector)
ES <13 = Insensitive
ES
≥13 = High Compensation
●
Sensor mode 1 (heat detector)
A1R
●
Sensor mode 2 (smoke detector)
Universal
FDOOT241-A9 in collective mode:
●
Sensor mode 0 (neural fire detector)
High Compensation
●
Sensor mode 1 (heat detector)
A1R
●
Sensor mode 2 (smoke detector)
Universal
FDOOT241-A3 in AnalogPLUS mode:
●
As DO1131A
Sensitive
●
As DOT1131A
Fast Response
●
As DT1131A
A1R
●
As DT1132A
BS
FDOOT241-A4 in SIGMALOOP mode:
●
In SIGMALOOP mode the sensor evaluation
takes place in the control panel
-