background image

Yayın Tarihi: 

12/06/2018 

Rev:03 

 

Important Warnings 

General 

 

Before using the device read this manual carefully. Keep it just in case of necessity. 

 

Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.

 

 

 

Keep the devices away from water and moisture 

 
 

 

 
 

 
Service 

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. 

 
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical 

interventions have to be done by technicians of company. 

 
 

 
 
 

Malfunctions that require technical service 

In case of any malfunction or below conditions contact with your authorized service,  

 

When Mains cable or the plug is harmed,  

 

Contact of device with a fluid,  

 

Exposure of rain and water,  

 

Fell down of device or harmed outer cover,  

 

Serious performance fall on the device,  

 

Depending on the instructions stated in manual, if your device not working properly 

Contact with your authorized service in such terms.  

 

Maintenance on your own  

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any 

defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have 
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are 

allowed for cleaning 

 

Transportation 

Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions 

that caused by improper transportation is not under warranty. 

 

Human and Environmental Health 

This device contains no chemical or biological elements that could harm human condition.  

 

 
 
 
 
Technical Features

 

 

 

TFS-3191 

Power Input 

24VDC 

 28VDC 

Alarm Current Consumption 

~15 mA ( @24VDC ) 

Sound Level 

100 dB 

±

2 dB (24VDC,@ 1 m) 

Sounder Type 

Type A device 

Piezo 

Piezzo with leakproof seal 

IP Class 

IP21C 

Operating Temperature Range 

-10

C ~ 55

Usage Area 

Internal indoor use 

Humidity 

+40°C

 between %0 to %95 Max 

Dimensions (mm) 

Ø:110mm, h:55mm

 

Housing Material 

Red , UL94 fireproof ABS 

Used Cable Cut 

0.28mm ² ~ 1.5mm ²

 

Weight (incl. Base / excluding 

base) 

 

 

 
 

Terminals

 

 

Number 1 

To next siren Negative (-)power out 

Number 2 

Negative (-)power input 

Number 3 

To next siren Positive (+)power out 

Number 4 

Positive (+) power input 

 

 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 

 
 

 
 

 
 

 
 

Warning:

 Do not attempt to remove the electronic board from its plastic case. The electronic board is 

closed for your safety. Users should avoid from interference. 

 