7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
123 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Collective maximum current connection factor/alarm verification
(FDOOT241-9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Use as
Parameter set
Maximum
current
connection
factor for
ES < 30
Maximum
current
connection
factor for
ES
≥
30
1
Alarm verification
on control panel
permitted with
detector ES < 13
(verification time at
the control panel
≥50
s)
Alarm verification on control
panel permitted with detector
ES
≥
13 (verification time at the
control panel ≥
30 s)
No.
Designation
Neural fire
detector
(FDOOT)
2
Robust
2
1.5
No
Yes
4
Balanced
5
Suppression
6
Fast Response
2
1.5
Yes
Yes
7
High Compensation 2
1.5
2
No
Yes
0 (ES
≥13)
High Compensation –
1.25
2
–
Yes
0 (ES <13) Insensitive
1.5
–
No
–
8
High Suppression
–
1.5
–
Yes
9
High Sensitive Fast –
1.5
–
Yes
Wide-
spectrum
smoke
detector
(FDO)
0
Universal
2
1.5
No
Yes
1
Universal
2
Robust
3
Sensitive
2
1.5
Yes
Yes
Heat detector
(FDT)
0…4
All parameter sets
2
1.5
No
Yes
1
For CS1115, the maximum current connection factor values in the column apply for ES <30.
2
Different connection factors due to the different measuring cycles.