FC300 (can be installed in Zone 0)
"Intrinsic safety" type of protection
ATEX/IECEx
DEMKO 05 ATEX 138072X
II 1G Ex ia IIC T6…T3 Ga
cCSAus (Canada, USA)
Canada:
Class I Division 1.
Class I Div. 1 Grp. A, B, C, D.
Ex ia IIC T6…T3 IIC Ga
USA:
Class I Division 1.
Class I Div. 1 Grp. A, B, C, DA
AEx ia IIC T6…T3 IIC Ga
EU Declaration of Conformity
A5E31814816A/010
Pressure equipment
• 2014/68/EU Pressure Equipment Directive (PED)
• Canadian Registration Number (CRN)
MASS 2100 - compact version (can be installed in Zone 0, 20)
"Intrinsic safety" type of protection
ATEX/IECEx
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C Da (For dust applications (IIIC) the maxi‐
mum ambient temperature is limited to 100°C according
to IEC 60079-11 table 4.)
cULus (Canada, USA)
Canada:
Class I+II+III Division 1. Grp. A, B, C, D, E, F, G
Ex ia IIC T6…T3 Ga
Ex ia IIIC T135°C Da
USA:
Class I Division 1.
Class I+II+III Division 1. Grp. A, B, C, D, E, F, G.
AEx ia IIC T6…T3 Ga
AEx ia IIIC T135°C Da (For dust applications (IIIC) the max‐
imum ambient temperature is limitedto 100°C according
to IEC 60079-11 table 4.)
EU Declaration of Conformity
A5E31814816A/010
Pressure equipment
• 2014/68/EU Pressure Equipment Directive (PED)
• Canadian Registration Number (CRN)
Technical data
11.10 Certificates and approvals
SITRANS MASS 2100 & FC300 (FCT010/DSL)
Operating Instructions, 06/2020, A5E39788682-AB
115