System description
Topology
9
138 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
9.2.4 Operating tree
The following elements and settings are represented in the Operation tree:
● Global system configuration
● Display and operator units such as:
– ↑ Person Machine Interface (PMI)
– ↑ Floor repeater terminal and ↑ floor repeater display
– Mimic display
– Event printer
Global system configuration
The global system configuration has the following elements:
● Global behaviour
– Events (event configuration)
– Commands ('Access level' assignment)
The behavior set here is always valid unless a different behavior is set locally.
● Master clock: The master clock is automatically assigned to the first ↑ station
(address 1).
● Country settings: Settings are undertaken here for localization and changing
between summer and winter time.
↑ Person Machine Interface (PMI)
The PMI is a permanent part of the ↑ station. The following settings can be
configured in the Operation tree:
● Basic settings with definition of default access level for the key switch and time
period during which the display returns to the normal display from an operating
display.
● ↑ Visibility:
A detailed description of the visibility can be found in the corresponding
chapter.
– Standard visibility
– Standby visibility
– Expanded visibility
● LEDs for signaling events and statuses (causes):
– Event with defined, local visibility.
– Event with optional, global visibility on a particular element from the
Hardware tree, ↑ Detection tree, or ↑ Control tree.
● Standard keys:
Frequently used functions can be assigned to the configurable standard keys.
– Views, e.g. message indicator, customer text view, fire brigade view
– Commands, e.g. activate/deactivate, test, configuration ('Set PS MANNED',
'Switch to UNMANNED', etc.).
● Favorite keys:
The favorite keys are in the display menu. There is a maximum of eight favorite
keys of which three are preconfigured. Frequently used functions can be
assigned to the favorite keys.