Operation
ALARM Procedure
5
41 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
Procedure in the event of alarm
Step
Action / Condition
Consequence / Status
1
Press <Acknowledge> on the ↑ Person
Machine Interface
⇨ With 'AVC', countdown t2 for examining the cause
of 'ALARM' starts
2
Read top line on display
● 'Fire Brigade requested'
⇨ 'ALARM' is transmitted to the fire brigade
● 'Fire Brigade in' 'mm:ss'
⇨ 'ALARM' is transmitted to fire brigade in mm:ss
Remaining time is shown as Countdown
● 'Call Fire Brigade !' if:
– Remote transmission switched off
– Remote transmission blocked or
defective
– No remote transmission available
⇨ Fire brigade must be called by phone!
⇨ No automatic transmission to fire brigade
3
Press 'Show intervention text' <softkey 2> ' if
displayed
or press <Show intervention text> button
Press <Jump back>
⇨ Intervention text is displayed
⇨ Fire location is displayed
4
Read off fire location on display
5
Optional: Press <Alarm device> on the
Person Machine Interface (password
required)
⇨ Deactivates the acoustic ↑ alarm devices
6
Go to the fire location
7
Decide: MAJOR INCIDENT or ↑ minor
incident
Procedure in the event of a major incident or minor incident
Condition
MAJOR INCIDENT
↑ Minor incident
Fire brigade has been called
Save people
Guide the fire brigade to the fire
location
Fight the fire
Try to prevent fire brigade
deployment
'Fire Brigade in' 'mm:ss'
Countdown is running
Trigger the manual call point
immediately
or
Press <Alarm delay off>
Press <Reset> (password required)
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Call the fire brigade on the phone!
Press <Reset> (password required)
Reset
A password is required for resetting.
It may be necessary to air the room before 'Reset' is possible.
You can temporarily ↑ switch off elements that cannot be reset.