Operation
Switching off / Switching on
5
50 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
Selecting option
Execute commands
Jump to link
Show details
(3)
(4)
(5)
κ
Select 'Execute commands' option, continue with <ok>
Select command
OFF
Activate alarm indicator
Deactivate alarm indicator
(1)
(3)
(4)
κ
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select 'OFF' command
Command response
Execute command
OFF
Command executed
Switching on the 'Detector'
Proceed in the same way as when ↑ switching off 'Detector', but select the 'ON'
command as shown below.
Select command
ON
(2)
κ
Select 'ON' command
As an alternative, you can select the corresponding detector or 'Zone' via the
'Message summary' main menu item and the 'Isolations' message category and
switch it back on with the 'More Options', 'Execute commands', and 'ON' softkey.