Operation
ALARM procedure PMI with FBP [AU]
5
43 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
Procedure in the event of alarm
Step
Action / Condition
Consequence / Status
1
Press <Acknowledge> on the Person
Machine Interface
⇨ With 'AVC, countdown t2 for examining the cause
of 'ALARM' starts
2
Read top line on display
● 'Fire Brigade requested'
⇨ 'ALARM' is transmitted to the fire brigade
● 'Fire Brigade in' 'mm:ss'
⇨ 'ALARM' is transmitted to fire brigade in mm:ss
Remaining time is shown as Countdown
● 'Call Fire Brigade !' if:
– Remote transmission switched off
– Remote transmission blocked or
defective
– No remote transmission available
⇨ Fire brigade must be called by phone!
⇨ No automatic transmission to fire brigade
3
Only with PIN for the 2,2 access level:
Press <Softkey 2> 'Show intervention text'
or press <Show intervention text> button
Press <Jump back>
⇨ Intervention text is displayed
⇨ Fire location is displayed
4
Read off fire location on display
5
If alarm devices are activated:
Press <Silence Alarm> on the Person
Machine Interface
⇨ Deactivates the acoustic alarm devices
6
Go to the fire location
7
Decide: MAJOR INCIDENT or ↑ minor
incident
Procedure in the event of a major incident or minor incident
Condition
MAJOR INCIDENT
Minor incident
Fire brigade has been called
Save people
Guide the fire brigade to the fire
location
Fight the fire
Try to prevent fire brigade
deployment
'Fire Brigade in' 'mm:ss'
Countdown is running
Trigger the manual call point
immediately
or
Press <Alarm delay off>
Press <Reset>
1
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Call the fire brigade on the phone!
Press <Reset>
1
1
Before resetting, the acoustic alarm devices must be deactivated. See Step 5.
Reset
It may be necessary to air the room before 'Reset' is possible.
You can temporarily ↑ switch off elements that cannot be reset.