11.4
FC124-ZA calculation
Type
Description
Standby
[mA]
Alarm
[mA]
Panel (internally)
Sounders, etc…
Standby
[mA]
Alarm
[mA]
Standby
[mA]
Alarm
[mA]
FC124-ZA
12 zone panel
118
187
Out 1 (e.g. Sounders)
Out 2 (e.g. Sounders)
Aux. output
Accessory cards
FCA1203-Z1
(1st)
Output card 2M 2R
12
25
Out A&B (e.g. Sounders)
FCA1203-Z1
(2nd)
Output card 2M 2R
12
25
Out A&B (e.g. Sounders)
FCA1203-Z1
(3rd)
Output card 2M 2R
12
25
Out A&B (e.g. Sounders)
FTO1202-Z1
Zone indicator field 12*2
1
2.5
FTO1203-H1
EVAC Module
0.5
2.2
Standby current [A]
Alarm current [A]
If the total current of the outputs (Sounders, etc.) is higher than
1000 mA
, then an
external power supply is required. In order to reduce the total current:
-
Power the output A&B from the external power supply (possible per card).
-
Move the Auxiliary output to the external power supply.
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max. 17 Ah)
_ _ h × 0._ _ _ A
+ 0.5 h × _._ _ _ A
× 1.25
=
Standby time [h]:
24, 30 or 72
Alarm time [h]:
0.5 hour
Aging factor:
1.25
Standby current [A]:
Total current in standby mode
Alarm current [A]:
Total current in alarm mode
Capacity [Ah]:
7 Ah; 12 Ah; 17 Ah