7.2.4
User interface
Lamp test available at
access level 2
If selected, the lamp test function is only available at access level 2.
Otherwise it is available at access levels 1 and 2.
Silence key with
EVAC function
If selected, all sounder control lines can be activated by pressing
the button <Silence / resound> if access level 2 is achieved.
Silence on ACK
If selected, all sounder lines can be silenced by <ACK>.
ACK available at
access level 1
If selected, the button function <ACK> is available in access level 1
in addition to the access level 2.
LED fire brigade
activated by alarm
dialer output
If selected, the LED is activated when the output 'Alarm dialer' is
active. Otherwise, the LED is activated by general alarm.
LED fire brigade
activated via input
If selected, the LED is activated if the dialer device confirmation
signal is given.
Display view
Standard: Fulfills EN 54-2
UK only FC122: 4 zones without customer text are displayed.
7.2.5
Zone options
Device coincidence
inhibit time
The fire condition is achieved with the second detector activation in
the same zone only. The inhibit time, between the first and the
second activation can be set to from 15 to 60 seconds. The higher
the value, the more reliable the application.
7.2.6
Output options
Pulse time
Fire alarm: Select the time for switch on / off for the respective
outputs. Value range : On 0 - 3 sec. Off 0 - 5 sec.
Alert: Select the time for switch on / off for the programmed outputs.
Value range: On 0 - 3 sec. Off 0 - 5 sec.
Resound on new
alarm
If selected, the sounder line will resound with a new alarm.
7.2.7
Mains power
Fault delay time
Delay time for Mains power fault. Time delay up to 30 min. selectable
in 5 min. steps.
Mains
power
Output
options
Zone
options
User