14
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
3.3
Technical data
You will find information on approvals, CE marking, and the relevant EU directives for
this device (these devices) in the following document(s); see 'Applicable documents'
chapter:
·
Document A6V10371354
FC121-ZA
FC122-ZA
FC123-ZA
FC124-ZA
Zones
Number of zones
2
4
8
12
Number of detectors per zone
Up to 32
Up to 32
Inputs
Number of inputs
2
3
Outputs
Number of monitored outputs
- Mainboard
2
2
- Output cards (Optional)
2
4
6
Number of relay outputs
- Mainboard
1
1
- Output cards (Optional)
2
4
6
Number of optional output cards
1
2
3
Alarm counter
9999 alarms
9999 alarms
History log
1000 events
1000 events
3.3.1
Electrical data
FC121-ZA
FC122-ZA
FC123-ZA
FC124-ZA
Zone
Operating voltage
- Standard zone
- GB continuity zone
DC 16.5…19 V
DC 21…28.6 V
DC 16.5…19 V
DC 21…28.6 V
Line resistance / capacitance
Collective & Conventional
device
- GB continuity
- Mixed zone
Used Conventional device
- Standard
- Short=alarm
Collective & Conventional
device
- Standard
- Short=alarm zone
≤
50
Ω
/
≤
1
μ
F
1,2,4,6
≤
50
Ω
/
≤
1
μ
F
1,2,4,6
≤
100
Ω
/
≤
1
μ
F
1,2,4,5
≤
100
Ω
/
≤
1
μ
F
1,4
≤
80
Ω
/
≤
1
μ
F
1,2,3,4,5,6
≤
80
Ω
/
≤
1
μ
F
1,3,4
≤
50
Ω
/
≤
1
μ
F
1,2,4,6
≤
50
Ω
/
≤
1
μ
F
1,2,4,6
≤
100
Ω
/
≤
1
μ
F
1,2,4,5
≤
100
Ω
/
≤
1
μ
F
1,4
≤
80
Ω
/
≤
1
μ
F
1,2,3,4,5,6
≤
80
Ω
/
≤
1
μ
F
1,3,4
1
Detector 110-series;
2
Detector FDOOT241-X, OOH740, FDF221-9, FDF241-9, FDL241-9;
3
Detectors series DS11, Synova Series 600C;
4
Synova Series 300C;
5
Conventional MCP;
6
Collective MCP
Alarm trigger
Z-Diode 5.6 V or resistor 410…820
Ω
Z-Diode 5.6 V or resistor 410…820
Ω