A6V10393190_h_en_--
2019-09-01
6.1.1
Procedure without Alarm verification
The Alarm dialer is activated in the event of a fire alarm.
Press the <ACKNOWLEDGE> button.
If the alarm event is acknowledged, the panel
turns off the panel buzzer.
è
Access level 2 password is required.
Optional: Silence the sounder lines by pressing
<
RESOUND / SILENCE
>
button.
MAJOR INCIDENT
: A real fire emergency
Check if the fire brigade called.
MINOR INCIDENT
: No fire alarm
Reset the system to quiescent mode by pressing
<RESET> button.
è
Access level 2 password is required.
Inform the fire brigade about the actual situation.
Notice
The fire alarm reoccurs if any device remains in fire condition.