28
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
In order to detect the creeping effect (supervision), the line must be calibrated during the
commissioning process. A line fault is indicated if the resistance is higher than calibrated.
The range of the line resistance including the relay is between 200-1000
Ω
.
Application:
With EOL diode: Sounder controls, fire outputs and alarm dialer.
With monitored relay for fault dialer: Only OUT A is specified to supervise the device
relay, see details in chapter 4.4.4.
Technical:
-
Max. current 24 V / 1 A
-
Line resistance max. 35
Ω
-
Each line must be terminated with EOL element (Diode 1N4007)
Programming:
-
Configure
g
Output
g
Output 4 – n
g
Mode
g
e.g. Sounder control
-
Configure
g
Output
g
Output 4 – n
g
Supervision EN 54-13
-
Configure
g
Output
g
Output 4 – n
g
Calibrate line
4.4.3
Relay
Relay outputs are used for controls without line monitoring.
Application:
LED indication on a remote terminal
Technical:
-
Max. current 30 V / 1 A
Programming:
-
Configure
g
Output
g
Output 6 – n
g
Mode
g
Fire output