26
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
4.4
Outputs
Outputs are used to transmit system status information. As a result three different types
are available: Monitored, Supervised and Relay.
4.4.1
Mainboard (OUT1 / OUT2)
Functionality 'Monitored line':
The panel monitors the line in terms of open and short circuits from the panel to the
EOL element.
Application:
Sounder controls, fire outputs and dialer
Technical:
-
Max. current
FC121-ZA and FC122-ZA
à
24 V / 0.5 A
FC123-ZA and FC124-ZA
à
24 V / 1 A
-
Each line must be terminated with EOL element (Diode 1N4007)
-
Supervised functionality: Not available
Programming
:
-
Configure
g
Output
g
Output 1 – n
g
Mode
g
Sounder control
4.4.2
Output card (OUTA / OUTB)
The output can be either programmed as 'Monitored' or 'Supervised'.
Functionality 'Monitored line':
The panel monitors the line in terms of open and short circuits from the panel to the
EOL element.
Application:
Sounder controls, fire outputs and dialer
Technical:
-
Max. current 24 V / 1 A
-
Each line must be terminated with EOL element (Diode 1N4007)
Programming:
-
Configure
g
Output
g
Output 4 – n
g
Mode
g
Sounder control
COM NO
OUT1
OUT3
–
+
OUTA OUTB
OUTC
OUTD
OUT2
+
–
EOL
EOL
COM NO
NC
COM NO
NC
–
+
–
+
–
+
Mainboard
Monitored
Relay
Output card
Monitored or
Supervised
Relay