22
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
4.3
Zone modes
4.3.1
Standard
The Standard line supports collective and conventional devices within the same zone.
Technical:
-
Each line must be terminated with EOL element Transzorb diode (18 V TVS).
-
Max. 32 devices on each line
Programming:
-
Configure
g
Zone
g
Zone 1 – n
g
Mode
g
Standard
Zone mode 'Standard' complies with EN 54-2 and EN 54-13.
+
+
+
+
–
+
AUX 24V
ZONE1 . . . . . . ZONE n
–
+
–
+
–
+
1a
1b
5
6
1a
1b
5
6
EOL
1a
1b
5
6
EOL
+
+
EOL