Functions
7.8 Analog Input Setup
FUP1010 IP67 Portable
94
Operating Instructions, 03/2012, A5E02951522-02
Vo Output Functions
The Vo analog output is a 0-10 VDC signal that varies linearly in relation to a selected
function.
Assigning a function to the voltage output:
1.
From the [Analog Out Setup] menu, press <Right Arrow] to access the [Vo1] option list.
2.
Move the cursor to the desired data function by pressing <Up/Down Arrow>.
3.
To store selection press <ENTER>.
Note
Refer to drawing 1010N-7-7 for Analog output connections.
Pgen Output Functions
The Pgen analog output is a buffered TTL-compliant pulse rate signal that varies linearly
from 0-5000 Hz in relation to a selected data function.
Assigning a function to the Pgen output:
1.
From the [Analog Out Setup] menu, press <Right Arrow> to access the [Pgen] option list.
2.
Move the cursor to the desired data function by pressing <Up/Down Arrow>.
3.
To store selection press <ENTER>.
7.8
Analog Input Setup
Analog Input Setup
Note
Some versions of the FUP1010 portable flow meter have the ability to read analog input
signals. The [Analog Inp Setup] menu cell is not displayed if the operating system of your
model does not include this facility.
The optional Analog Input Setup function assigns an active analog input to a measurement
channel/path. The flow meter provides two DC current (4-20mA) and two voltage (0-10V)
input ports for single channel, Dual Channel and Dual Path units. The DC current input
ranges from a zero level of 4mA to a full scale of 20mA and allows you to enable this port
and then span it to any desired scaling.
Содержание 7ME3510
Страница 2: ......
Страница 10: ...Table of contents FUP1010 IP67 Portable 8 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 68: ...Connecting 5 3 Zero Flow Adjust Menu FUP1010 IP67 Portable 66 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 116: ...Functions 7 11 Reflexor FUP1010 IP67 Portable 114 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 144: ...Technical data 11 1 Technical Data FUP1010 IP67 Portable 142 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 159: ...1010WP 7 21614 C ...
Страница 160: ...1010WP 7 21614 C ...
Страница 161: ...1010WDP 7 21614 C ...
Страница 162: ...1010WDP 7 21614 C ...
Страница 163: ......
Страница 164: ......
Страница 165: ......
Страница 167: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Страница 168: ......
Страница 169: ...21614 C ...
Страница 170: ......
Страница 171: ......
Страница 172: ......
Страница 173: ......
Страница 174: ...21614 C ...
Страница 175: ...21614 C ...
Страница 176: ...21614 C ...
Страница 177: ...21614 C ...
Страница 178: ...21614 C ...
Страница 179: ...21614 C ...
Страница 180: ...21614 C ...
Страница 181: ......
Страница 182: ......
Страница 183: ...21614 C ...
Страница 184: ...21614 C ...
Страница 185: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Страница 186: ...REFLECT MODE DIRECT MODE 21614 C ...
Страница 187: ...1015BC 1 8 21614 C ...
Страница 188: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Страница 189: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Страница 190: ......
Страница 191: ......
Страница 192: ......
Страница 193: ......
Страница 195: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Страница 196: ......
Страница 197: ......
Страница 198: ...L TEMPERATURE BELOW 225 F ONLY SUITABLE FOR AMBIENT TEMPERATURE GLAND SUPPLIED WITH CABLE IS 21614 C PART No L ...
Страница 208: ...Glossary FUP1010 IP67 Portable 162 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 212: ...Index FUP1010 IP67 Portable 166 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 213: ......