Troubleshooting
10.1 Troubleshooting
FUP1010 IP67 Portable
124
Operating Instructions, 03/2012, A5E02951522-02
Error or Message
Probable Cause
Solution
Re-space Index
The measured liquid sonic velocity (Vs) is
more than +/- 25% of the average Vs range.
Ensure proper pipe dimensions and/or Liquid
data entries are correct.
Properly enter correct Sensor Size into the
meter [Install Sensor] menu.
Confirm sensor spacing is correct by checking
[Install Sensor] menu spacing parameters.
Invalid Setup (use
Direct Mode)
During the Initial Makeup the system
detects invalid Sensor spacing, erroneous
liquid or pipe parameters, or some other
factor that prevents it from completing the
Initial Makeup.
This may be due to one of the following:
An out-of-range data entry.
An invalid condition (e.g., overlapping Sensors
in Reflect Mode). If selecting Direct Mode does
not resolve, review all site setup and Sensor
installation choices; particularly data entered
for pipe and liquid.
In Reflect Mode the flow meter detects that the
pipe wall signal may impinge upon the liquid
signal. Use Direct Mode instead.
Press <ENTER>, <Up Arrow>, <Down Arrow>,
or <Left Arrow> to abort install routine.
Continue programming other site data in
anticipation of resolving the difficulty later. Call
technical support for help if necessary.
Low Signal - Press
<ENTER>
During the Initial Makeup the flow meter
decides that the level of the receive signal is
insufficient for proper operation.
Some reasons for low signal are:
Invoking [Install Complete?] on an empty pipe.
Coupling compound insufficient; not applied or
evaporated. Reapply couplant.
A disconnected or broken Sensor cable.
The pipe needs to be conditioned at the
mounting location.
Flush out large air bubbles.
The Sensor cables are defective or not
connected to the correct channel.
The Set Empty routine performed when pipe
was NOT actually empty.
If you locate and correct the improper condition
immediately, press <ENTER> to resume the
installation procedure. Otherwise, press the <Left
Arrow> to abort the installation and conduct a
thorough investigation.
Detection Fault
If it appears that the flow meter cannot
complete an Initial Makeup it means that the
pipe and/or liquid conditions do not permit a
receive signal that meets the flow detection
standards. The system will not operate.
Attempt to improve operating conditions by
reinstalling the Sensors at a different spacing
offset, or even at a different location on the pipe.
Switching from Reflect to Direct Mount may solve
the problem. However, operation may not be
possible if there is poor liquid or pipe wall sonic
conductivity.
Содержание 7ME3510
Страница 2: ......
Страница 10: ...Table of contents FUP1010 IP67 Portable 8 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 68: ...Connecting 5 3 Zero Flow Adjust Menu FUP1010 IP67 Portable 66 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 116: ...Functions 7 11 Reflexor FUP1010 IP67 Portable 114 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 144: ...Technical data 11 1 Technical Data FUP1010 IP67 Portable 142 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 159: ...1010WP 7 21614 C ...
Страница 160: ...1010WP 7 21614 C ...
Страница 161: ...1010WDP 7 21614 C ...
Страница 162: ...1010WDP 7 21614 C ...
Страница 163: ......
Страница 164: ......
Страница 165: ......
Страница 167: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Страница 168: ......
Страница 169: ...21614 C ...
Страница 170: ......
Страница 171: ......
Страница 172: ......
Страница 173: ......
Страница 174: ...21614 C ...
Страница 175: ...21614 C ...
Страница 176: ...21614 C ...
Страница 177: ...21614 C ...
Страница 178: ...21614 C ...
Страница 179: ...21614 C ...
Страница 180: ...21614 C ...
Страница 181: ......
Страница 182: ......
Страница 183: ...21614 C ...
Страница 184: ...21614 C ...
Страница 185: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Страница 186: ...REFLECT MODE DIRECT MODE 21614 C ...
Страница 187: ...1015BC 1 8 21614 C ...
Страница 188: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Страница 189: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Страница 190: ......
Страница 191: ......
Страница 192: ......
Страница 193: ......
Страница 195: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Страница 196: ......
Страница 197: ......
Страница 198: ...L TEMPERATURE BELOW 225 F ONLY SUITABLE FOR AMBIENT TEMPERATURE GLAND SUPPLIED WITH CABLE IS 21614 C PART No L ...
Страница 208: ...Glossary FUP1010 IP67 Portable 162 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 212: ...Index FUP1010 IP67 Portable 166 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 213: ......