Connecting
5.2 Sensor Wiring
FUP1010 IP67 Portable
28
Operating Instructions, 03/2012, A5E02951522-02
5.2
Sensor Wiring
5.2.1
Preliminary Installation Procedures
Reflect and Direct Sensor Mounting
Reflect and Direct mounting modes are supported for clamp-on sensors. The flow meter
recommends a mounting mode after analyzing your pipe and liquid data entries.
Note
When installing sensors, do not key in the V/M (Version/Modification) label number as the
Sensor Size.
Clamp-on Sensor Mounting Modes
The transmitter recommends a mounting mode after analyzing your pipe and liquid data
entries. However, you can install clamp-on sensors in the way that best suits your application
and the sensor type you have purchased.
①
④
Upstream Sensor
Sonic Path
②
Flow Direction
⑤
Pipe
③
Downstream Sensor
Figure 5-2
Reflect Mount (Pipe shown from above in 12 o'clock position)
Reflect mount is recommended whenever possible. This is the simplest way to mount the
sensors. Also, Reflect mount resists abnormal flow profile conditions such as cross-flow
within the flow stream. Reflect mount supports the AutoZero function, which zeroes the flow
meter automatically without user-participation. In addition, Reflect mount may be the only
possibility if conditions do not allow access to the opposite side of the pipe.
Содержание 7ME3510
Страница 2: ......
Страница 10: ...Table of contents FUP1010 IP67 Portable 8 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 68: ...Connecting 5 3 Zero Flow Adjust Menu FUP1010 IP67 Portable 66 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 116: ...Functions 7 11 Reflexor FUP1010 IP67 Portable 114 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 144: ...Technical data 11 1 Technical Data FUP1010 IP67 Portable 142 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 159: ...1010WP 7 21614 C ...
Страница 160: ...1010WP 7 21614 C ...
Страница 161: ...1010WDP 7 21614 C ...
Страница 162: ...1010WDP 7 21614 C ...
Страница 163: ......
Страница 164: ......
Страница 165: ......
Страница 167: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Страница 168: ......
Страница 169: ...21614 C ...
Страница 170: ......
Страница 171: ......
Страница 172: ......
Страница 173: ......
Страница 174: ...21614 C ...
Страница 175: ...21614 C ...
Страница 176: ...21614 C ...
Страница 177: ...21614 C ...
Страница 178: ...21614 C ...
Страница 179: ...21614 C ...
Страница 180: ...21614 C ...
Страница 181: ......
Страница 182: ......
Страница 183: ...21614 C ...
Страница 184: ...21614 C ...
Страница 185: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Страница 186: ...REFLECT MODE DIRECT MODE 21614 C ...
Страница 187: ...1015BC 1 8 21614 C ...
Страница 188: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Страница 189: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Страница 190: ......
Страница 191: ......
Страница 192: ......
Страница 193: ......
Страница 195: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Страница 196: ......
Страница 197: ......
Страница 198: ...L TEMPERATURE BELOW 225 F ONLY SUITABLE FOR AMBIENT TEMPERATURE GLAND SUPPLIED WITH CABLE IS 21614 C PART No L ...
Страница 208: ...Glossary FUP1010 IP67 Portable 162 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 212: ...Index FUP1010 IP67 Portable 166 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 213: ......