Connecting
5.2 Sensor Wiring
FUP1010 IP67 Portable
52
Operating Instructions, 03/2012, A5E02951522-02
1.
Perform all required menu steps up until the point where you respond to the [Install
Complete?] prompt.
2.
Make a note of the Number Index. Check to ensure that you have a matched set of
sensors. They both should have the same S/N number but marked with either an "A" or
"B" (e.g., 100A and 100B).
Note
Index pins are used as stops against each sensor inserted at the reference hole for one
sensor and the Number Index hole for the other sensor (see
⑨
in figure below).
①
⑥
Tension Screw
Pipe
②
To SITRANS F 1010 Flow meter
⑦
Ultrasonic Couplant
③
1012C Series Cable
⑧
Number Index hole pin
④
Sensor Clamp
⑨
1012TP Series Mounting Track
⑤
Upstream and Downstream Sensors
⑩
Flow direction
⑪
REF Hole Index Pin
Figure 5-23 Reflect Mount with Model 1012TP Mounting Track (Side View)
3.
Place the track rail assembly on the top surface of the pipe at the location where you
have determined it will be mounted. Ensure that it is a smooth area without any raised
spots or seams.
Содержание 7ME3510
Страница 2: ......
Страница 10: ...Table of contents FUP1010 IP67 Portable 8 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 68: ...Connecting 5 3 Zero Flow Adjust Menu FUP1010 IP67 Portable 66 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 116: ...Functions 7 11 Reflexor FUP1010 IP67 Portable 114 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 144: ...Technical data 11 1 Technical Data FUP1010 IP67 Portable 142 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 159: ...1010WP 7 21614 C ...
Страница 160: ...1010WP 7 21614 C ...
Страница 161: ...1010WDP 7 21614 C ...
Страница 162: ...1010WDP 7 21614 C ...
Страница 163: ......
Страница 164: ......
Страница 165: ......
Страница 167: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Страница 168: ......
Страница 169: ...21614 C ...
Страница 170: ......
Страница 171: ......
Страница 172: ......
Страница 173: ......
Страница 174: ...21614 C ...
Страница 175: ...21614 C ...
Страница 176: ...21614 C ...
Страница 177: ...21614 C ...
Страница 178: ...21614 C ...
Страница 179: ...21614 C ...
Страница 180: ...21614 C ...
Страница 181: ......
Страница 182: ......
Страница 183: ...21614 C ...
Страница 184: ...21614 C ...
Страница 185: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Страница 186: ...REFLECT MODE DIRECT MODE 21614 C ...
Страница 187: ...1015BC 1 8 21614 C ...
Страница 188: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Страница 189: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Страница 190: ......
Страница 191: ......
Страница 192: ......
Страница 193: ......
Страница 195: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Страница 196: ......
Страница 197: ......
Страница 198: ...L TEMPERATURE BELOW 225 F ONLY SUITABLE FOR AMBIENT TEMPERATURE GLAND SUPPLIED WITH CABLE IS 21614 C PART No L ...
Страница 208: ...Glossary FUP1010 IP67 Portable 162 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 212: ...Index FUP1010 IP67 Portable 166 Operating Instructions 03 2012 A5E02951522 02 ...
Страница 213: ......