IV319 Rev.00
Data 2010-06-22
Pag. 32 di 118
6. Operation
6.1 Operation Mode
1. Turn on the UPS with utility power supplied (in Line mode)
1) After you make sure that the power supply connection is correct,
and then set the breaker of the battery box in the
³
ON
´
position
(this step only for long backup time model), after that set the
input breaker in the
³
ON
´
position. At this time the fan rotates
and the UPS supplies power to the load via the bypass. The
UPS operates in Bypass mode.
2) To power on the UPS by simply pressing the ON button
continuously for more than 1 second, the buzzer will beep
once.
3) A few seconds later, the UPS turn into Line mode. If the utility
power is abnormal, the UPS will operate in Battery mode
without output interruption of the UPS.
2. Turn on the UPS with no utility power supplied (in Battery
mode)
1) After you make sure that the breaker of the battery box is in the
³
ON
´
position (this step only for long backup time model).
2) Press the ON button continuously for more than 1 second to
power on the UPS, and the buzzer will beep once, UPS
operates in No Output mode.
3) A few seconds later, the UPS turn into Battery mode.
3. Turn off the UPS with utility power supplied (in Line mode)
1) To turn off the inverter of the UPS by pressing the OFF button
continuously for more than 1 second, and the buzzer will beep
once. The UPS will turn into Bypass mode.
Содержание Green Point 6 20KVA
Страница 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Страница 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Страница 55: ...IV319 Rev 00 Data 2010 06 22 Pag 55 di 118 STEP 5 The output voltage would be 230VAC after the UPS is turned on...
Страница 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Страница 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...