IV319 Rev.00
Data 2010-06-22
Pag. 46 di 118
The UPS does not have the backup function when it is in Bypass
mode. The power used by the load is supplied from the utility
power via internal filter.
10.3 Line mode
The LCD display in Line mode is shown in the following diagram.
The information about the utility power, the battery, the UPS output
and the load could be displayed. The symbol of
³
´
and
³
´
indicates the UPS is working in line mode.
Line mode
If output overloaded, the
³
OVER LOAD
´
is shown and the UPS will
beep twice every second. You should get rid of some unnecessary
loads one by one to decrease the loads connected to the UPS less
than 90% of its nominal power capacity.
Note:
Please follow the following steps to connect the generator
᧶
Ⴠ
Activate the generator and wait until the operation is stable
before supplying power of the generator to the UPS (be sure
that the UPS is in idle mode). Then turn on the UPS according
to the start-up procedure. After the UPS is turned on, then the
loads can be connected to the UPS one by one.
Ⴠ
The power capacity of the AC generator should be at least twice
Содержание Green Point 6 20KVA
Страница 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Страница 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Страница 55: ...IV319 Rev 00 Data 2010 06 22 Pag 55 di 118 STEP 5 The output voltage would be 230VAC after the UPS is turned on...
Страница 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Страница 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...