Appendix 1: The Corresponding Form of the LCD
Display
No.
Operating state
LCD Code
Display
Alarm warning
1
No Output mode
Pn*
None
2
Bypass mode
Pn*
Beep once every 2 min.
3
Line mode
Pn*
None
4
Battery
mode
0~20% Battery
capacity
Pn*
Beep once every sec
21%~100% Battery
capacity
Beep once every 4 sec
5
Battery Test mode
Pn*
None
6
Overloaded in Bypass mode
Pn*
Beep twice every sec.
7
Overloaded in Line mode
Pn*
Beep twice every sec.
8
Overloaded in Battery mode,
Early-warning
Pn*
Beep twice every sec.
9
BUS voltage abnormal
05
Continuously beep
10
INV abnormal
06
Continuously beep
11
Overloaded and cut off the output
07
Continuously beep
12
Over temperature
08
Continuously beep
13
Output short circuited
09
Continuously beep
14
Communication abnormal
10
Continuously beep
15
Battery open
11
Continuously beep
16
INV relay failed
12
Continuously beep
17
BAT SCR failed
14
Continuously beep
18
Parallel abnormal
15
Continuously beep
19
ID abnormal
21
Beep once every 10 sec
20
Fan abnormal
22
Beep once every sec
21
Charger and battery failed
23
Beep once every sec
*
Note
: Pn indicate
the quantity of the parallel system
Содержание Green Point 6 20KVA
Страница 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Страница 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Страница 55: ...IV319 Rev 00 Data 2010 06 22 Pag 55 di 118 STEP 5 The output voltage would be 230VAC after the UPS is turned on...
Страница 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Страница 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...