IV319 Rev.00
Data 2010-06-22
Pag. 14 di 118
3) Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0 C-40 C
<95%
<1000m
UPS only -20 C
±
+55 C
Battery -5°C
±
+40°C
Note:
if the UPS is installed or used in a place where the altitude is
above than
1000m
, the output power must be derated in use, please
refer to the following:
Altitude (M)
1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating
Power
100% 95%
91%
86%
82%
78%
74%
70%
67%