9
Operation
This chapter describes the operation of the UE410 Safeguard Detector Box safety sys‐
tem.
These operating instructions do not provide information on operating the machine in
which the UE410 Safeguard Detector Box safety system is integrated.
9.1
Status indicators of the UE410-SD
Table 3: Status indicators of the UE410-SD
LED
Display
Relevance
PWR
Off
No supply voltage
Green
Supply voltage is on
Q1
Off
Safety outputs Q1/Q2 are ow
Green
Safety outputs Q1/Q2 are high
RES
REQ
Flashing green (1 Hz)
Reset required after interruption
Flashing green (2 Hz)
Reset required after process error or discrepancy error
ERR
Flashing red
Error,
see "UE410-SD fault diagnosis", page 36
Red
Error,
see "UE410-SD fault diagnosis", page 36
I1
Green
Operating mode with sensor pair A
Off
Operating mode with sensor pair A and sensor pair B
I2
Green
Output Q3 is configured for the connection of a higher-level
control (high)
Off
Output Q3 is configured for connection of a signal lamp (low)
I3
No function
I4
Flashing green
Reset pushbutton fault
Green
Reset pushbutton and EDM closed
I5 / I6
Green
Sensor pair A active (object detected)
Off
Sensor pair A switched off
Flashing green in
push-pull
Process error or discrepancy error at sensor pair A
I7 / I8
Green
Sensor pair B active (object detected)
Off
Sensor pair B switched off
Flashing green in
push-pull
Process error or discrepancy error at sensor pair B
9.2
Operating notes
Safety outputs Q1 and Q2
If the connected Safeguard Detector sensors do not generate a 10 Hz signal, safety out‐
puts Q1/Q2 switch off within the response time. For example, this is the case if the sen‐
sors do not detect any object or if there is a sensor error.
Application diagnostic output Q3 “reset required”
The application diagnostic output Q3 indicates the status
reset required
. Depending on
the configuration, a signal lamp or higher-level control can be connected to this output.
Input I2 is used for configuring output Q3.
OPERATION
9
8021417/2018-01-17 | SICK
O P E R A T I N G I N S T R U C T I O N S | UE410 Safeguard Detector Box
31
Subject to change without notice