Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 6, bit 0: IOPSO
Coding
0
Output data source invalid
1
Output data source valid
7.1.2.2.1.21
Port parameterization via web server
Port configured by PDCT
can be used to read out whether the parameterization via the
PDCT is defined for the port (
see "Port configuration mode", page 34
).
This setting can only be called up via the PLC interface.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 1, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 6, Bit 2: PDCT
Coding
0
Port parameterization via PLC
1
Port parameterization via web server
7.1.2.2.1.22
IOL_CALL
IOL_CALL
is an add-on to the PROFINET protocol that can be used to access
IO-Link
On-Request
data (ISDU parameters). It is specified in the document “IO-Link Integration
- Edition 2, Guideline for PROFINET” Version 1.0 - June 2017 (order no. 2.832) of the
PROFIBUS user organization (PNO).
IOL_CALL
can be located in a PLC as a function block (FB). The FB requires at least the
following parameters:
Parameter
Definition
ID
Address of one of the available IO-Link device submodules or the
IO-Link master submodule (IOLM subslot 2.1).
CAP
The Client Access Point (CAP) represents the PROFINET data set
index that provides the “tunnel” to the IO-Link system. The value of
this index is
46080
.
Port
Number of the IO-Link port on which the function is to be executed
(0 to 3). This value is not relevant if
IOL_CALL
is called via one of
the IO-Link device submodules, since a submodule is permanently
connected to a port.
RD/WR
Specifies whether the
On-Request
data is to be read (RD) or written
(WR).
IOL_Index
Index of the
On-Request
data or command code for the port func‐
tion
IOL_Subindex
Subindex of the
On-Request
data or command code for the port
function
IOL_Data
On-Request
data to be written to or read from the IO-Link device
7.2
Operation via Webserver
The SIG200 can be accessed via the integrated web server. To do so, an IP address
must be set for the SIG200. The SIG200 is shipped from the factory without a preset IP
address. The default setting for IP address assignment is made via the BOOTP protocol.
The following web browsers are supported:
•
Microsoft Internet Explorer (version 11 or higher)
•
Google Chrome (version 50 or higher)