Properties
Values
Process data
Max. 257 bytes at input and 257 bytes at output
Minimum cycle time: 1 ms
Asynchronous data
Are supported,
Observed standard
IEEE802.3u (100Base-Tx)
Conformity class
Class B
NetLoad class
II
Ethernet ports
2
PROFINET features
Media redundancy (MRP), network diagnostics (MIB/
SNMP), topology detection, connection diagnostics (for‐
ward/backward), link diagnostics (link length measure‐
ment), I&M0...3, automatic device replacement, gear
reduction, OpenVAS tested
GSDML file
Available in V2.2, V2.32, V2.33, V2.34
For the integration of the SIG200 into a PROFINET PLC, the corresponding GSDML file
(General Station Description Markup Language) must be used.
Download the GSDML file at
. Different versions are available for differ‐
ent engineering tools.
7.1.2.1
Device model
SIG200 PROFINET represents process data and acyclic data in the following slots:
The PROFINET slots have the following functions:
Slot
Subslot Name
Function
0
SIG200-0A0412200
Device Access Point (DAP): Main module
X1
PN-IO
PROFINET functions
X1 P1
Port 1 – M12
Ethernet port functions
X1 P2
Port 2 – M12
7
SIG200 CONFIGURATION
20
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
8017853.1D0S/2021-11-04 | SICK