4 User manual GC600-GC600
Mains
6.2
Pushbuttons
Function
MODE UP
MODE
DOWN
Ref. 1a
OFF/RESET
PROGRAM
The genset is disabled; all anomaly signals are disabled. All possible alarms
are reset. It is possible to access to the
parameter’s configuration.
MAN
(Manual)
The Gen-set control module is set for manual gen-set control.
Press the
START
button to start the engine.
Press the
STOP
button to stop the engine.
With the engine running and up to speed:
GC600
Press and hold down the
ESC/SHIFT
button
, and press the
GCB
button
for the manual open/close command of
MCB
circuit breaker
with possible synchronisation if configured in the plant.
Press the
GCB
button
for the manual open/close command of
GCB
circuit breaker with possible synchronisation if configured in the plant.
GC600
Mains
Press the
MCB
button
for the manual open/close command of
MCB
circuit breaker with possible synchronisation if configured in the plant.
Press the
GCB
button
for the manual open/close command of
GCB
circuit breaker with possible synchronisation if configured in the plant.
INFORMATION! For some types of plants, the sequences depend on
the Software and Hardware configuration of the plant during the installation
activity.
In case of voltage on BUS, the synchronization is required.
AUTO
(Automatic)
TEST
The controller automatically manages the genset operation, so it will be
started if required by the operating conditions.
By pressing the
START
button it is possible to activate/deactivate the
TEST
mode. If not differently configured, it does not cause the
GCB
circuit
breaker closure (with eventual opening of
MCB
).
WARNING! The STOP
button, causes the stop of the Generator
if running and the activation of a lockout unless configured otherwise.