S.16 (ANALOGUE INPUTS)
displays the value of the expansion modules analogue inputs. The
page is available only if one or more
DITEMP
or
DIGRIN
modules are installed in the system. If
more than 8
DITEMP/DIGRIN
are used, the controller shows them on two pages, letting them
alternate every 2 seconds: (keep
Esc/SHIFT
pressed to stop the rotation).
Page
S.17 (ANALOGUE INPUTS)
displays the value of the expansion modules analogue inputs. The
page is available only if the
DIVIT
expansion module is installed in the system.
If more than 3
DIVIT
are used, the controller shows them on two pages, letting them alternate every 2 seconds: (keep
Esc/SHIFT
pressed to stop the rotation).
The page
S.18 (ANALOGUE OUTPUTS)
displays the value of the controller analogue outputs and the
related function.
Pressing ENTER you pass to a viewing by function: the controller shows a list of functions really
associated to the analogue outputs, showing the analogue value related to each function,
independently from the output really associated to the functions. If more than 8 inputs/outputs are
configured on each page, the controller shows them all letting them rotate (8 at a time) every two
seconds: keeping the Esc/SHIFT button pressed, you stop the rotation.
The
S.19 (ANALOG OUTPUTS)
page displays the analogue output value of the
DANOUT
expansion
module. The page is available only if the
DANOUT
expansion module is installed in the system.
If more than 3
DANOUT
are used, the controller shows them on two pages, letting them alternate
every 2 seconds: (keep
Esc/SHIFT
pressed to stop the rotation).
The page
S.20 (MAINS PROTECTION)
is displayed only if the type of plant considers the temporary
parallel with the mains.
It displays the status of all protections of parallel with the mains. The disabled protections are not
displayed. For each protection enabled, the controller displays a text (for example “27<<”: it is
displayed in reverse if the protection is enabled - mains out of tolerance).
Possible codes are: “27<<”, “27<”, “27T”, “27Q”, “59>”, “59>>”, “81<<”, “81<”, “81>”, “81>>”,
“81R”, “VJ”, “MC” (by MC100), “DI” (by contact).
Page
S.21 (PULSE COUNTER)
is displayed only if the controller is configured as a pulse counter. From
version 01.19, it is in fact possible to count the activations/deactivations of the digital inputs, up
to a maximum of 8 counters. For this purpose, functions DIF.2401...DIF.2408 have been added
for configuring the digital inputs. When a configured input changes from "inactive" to "active", the
relative counter is incremented by 1. When the input configured with functions
DIF.2417...DIF.2424 is active, the relative counter is forced to zero.
You can scroll through the various pages using
the
LEFT
and RIGHT
buttons.
This mode displays all the information on the measurements taken by the Gen-set control module on
the electric lines.
Under some electrical measures, the controller also displays a bar showing graphically the value
measured compared to the rated power: on the bar are also one or more notches representing the
eventual thresholds. The colour with which the band is filled is green if the measure is in tolerance,
yellow if the measure is out of tolerance.
Page
M.01 (SYSTEM)
displays a wiring diagram of the system. The states of the switches, the
MAINS
, the
GENERATOR
, the
USERS
and the electrical values depend on the system
configuration.