28 User manual GC600-GC600
Mains
In
MAN
mode, the engine start/stop and
GCB
switch are carried out by the operator. By
pressing the “
GCB
” button for the connection of the genset, the synchronisation is activated;
GCB
is closed, and the load ramp is activated. When supplying, by pressing the
GCB
button
the sequence of power unload is activated and, once over, the
GCB
is opened. Press the
“
STOP
” button to stop the engine.
WARNING! As some slow power ramps may have been set, check the command
against the "Power reference" value shown in the same page and not against the value of
the power produced.
It is possible to manually regulate the power to supply without modifying directly the parameter that
defines the regulation power.
Display the page
M.01
(available only for MPM plants), press
ENTER
to change and the
buttons
LEFT
and
RIGHT
to select between “power required” and/or “cosphi
required”; use the button
UP
Ref. 1c
to increase the value and
DOWN
Ref. 1c
to
decrease the value set in percentage (%). The value that will be changed is highlighted in negative.
INFORMATION!
The value modified is acquired and saved without needing to confirm the
variation with the
ENTER
button.
Press the
ESC/SHIFT
button to exit the adjustment procedure.
INFORMATION!
Note: The described function is only available if no external potentiometer has
been configured for power regulation.
8.1
The Gen-set control module can display the texts in various languages.
To select a language different from that set, view the screen
S.03 (GEN-SET)
using the navigation
buttons. To change the
LANGUAGE
press
ACK/ENTER
: the square brackets [ ] will start
flashing. Use the
UP
and
DOWN
buttons to display the available LANGUAGES, then
press
ACK/ENTER
to confirm or
Esc/SHIFT
to cancel the changes.
8.2
The device includes an internal clock/calendar used primarily for the functions:
•
Weekly working hours of the generator set.
•
Calendar for the scheduled “
TEST
”.
•
Recording of events with date and time in the history logs.