8 User manual GC600-GC600
Mains
Signalling
Function
Ref. 2a
Flashing at 25% ON signals a COM error (J1939 or MTU): the
port is in
ERROR-PASSIVE
mode.
Flashing at 75% ON signals a COM error (J1939 or MTU): the
port is in
BUS-OFF
mode.
Indicates that the
CAN-BUS
has been disabled or that it is
enabled and operating, but no messages are received from the
engine and/or the expansion modules since at least 2 seconds.
Ref. 2a
PMCBus
STATUS
Indicates that the
CAN-BUS
interface is ON and in
ERROR-
ACTIVE
mode.
Power Management Communication Bus (PMCB).
Flashing at 25% ON signals a COM error (J1939 or MTU): the
port is in
ERROR-PASSIVE
mode.
Power Management Communication Bus (PMCB).
Flashing at 75% ON signals a COM error (J1939 or MTU): the
port is in
BUS-OFF
mode.
Power Management Communication Bus (PMCB).
Indicates that the
CAN-BUS
has been disabled.
Power Management Communication Bus (PMCB).
Ref. 2a
ENGINE
RUNNING
It indicates that the engine is running.
Flashing at 50% indicates that the engine is running, and the
cooling cycle is ongoing.
It indicates that the engine is idle.
Ref. 2b
MAINS LIVE
Mains
power is ON and stable in the tolerance range.
The
MAINS SIMULATION
digital input is enabled from the set
time.
The
Mains
power is OFF.
The
MAINS SIMULATION
digital input is disabled.
Flashes at 50% during transition between the previous two
states.
Flashing at 25% the
Mains
power is on but below the tolerance
range.
Flashing at 75% the
Mains
power is on but over the tolerance
range.
Ref. 2b
GENERATOR
LIVE
Generator
voltage and frequency are present and stead within
the tolerance range.
Generator
voltage and frequency are not present.
Flashes at 50% during transition between the previous two
states.
Flashing at 25% the Mains power and frequency are on but
below the tolerance range.
Flashing at 75% the Mains power and frequency are on but over
the tolerance range.
MCB
GC600
Mains
The MCB switch is opened.
The MCB switch is closed.