ENGLISH
78
Mod. MII
rev. 01
SETRONIC Verona
CHOICE OF CABLE TO USE FOR CONTROLLER - DETECTOR AND DETECTOR –
DETECTOR LINES
2
Ÿ
Minimum section of cable 0,5 mm ; use two cables with two wires following the national
standard for the chosen of type.
Ÿ
Maximum cable diameter 8 mm for cable gland PG9
Ÿ
Max capacity 60pF/m
Ÿ
Max resistance 50 Ohm/km
CAUTION FOR INSTALLATION
Ÿ
When the installation is in electrically noisy environment and/or with the presence of strong
currents, it is necessary to use a cable with two shielded bight cable (one for power supply
and one for the RS485).
Ÿ
It is clear that working to the limit of RS485 line, better features of cable must be considered.
Ÿ
Do not make junction along the lines
Ÿ
Be careful that the connection of the shield, if used, must be connected to the mass only in
one side, at the beginning or at the end of the line. Inside the socket of the detector, make a
bridge with the shield so that it is continuous from beginning to the end of the line.
Ÿ
The RS485 standard is made for the connection of many numbers of devices in multidrop
(daisy-chain). So that they are not allowed shunts or connection in T line mode. This means
that the wire must pass from the first to the second detector and so on up to the last one.
PARAMETER OF SIMPLE «AUTONOMOUS» ISOLATOR
Parameter
Value
Note
Vmax
32,0 V
max. line voltage
Vnom
27,2 V
nominal line voltage
Vmin
20,0 V
min. line voltage
RSOmax
25 Ω
max. line resistance at which the device isolates
(i.e. switches from “closed” to “open”)
RSOmin
10 Ω
min. line resistance at which the device isolates
(i.e. switches from “closed” to “open”)
RSCmax
50 Ω
max. line resistance at which the device reconnects
(i.e. switches from “open” to “closed”)
RSCmin
35 Ω
min. line resistance at which the device reconnects
(i.e. switches from “open” to “closed”)
ILmax
140 mA
max. leakage current with the switch open (isolated
state)
Содержание ILIA ERHSO712
Страница 1: ......
Страница 3: ...ENGLISH MANUAL ...
Страница 4: ......
Страница 6: ...HIGH SENSITIVITY LINEAR BEAM DETECTOR MODEL ERHS0712 ENGLISH 50 Mod MII rev 01 SETRONIC Verona ...
Страница 15: ...HIGH SENSITIVITY REFLECTION SYSTEM DETECTOR MODEL ERRHS0712 ENGLISH Mod MII rev 01 SETRONIC Verona 59 ...
Страница 24: ...CONTROLLER FOR BEAM DETECTOR MODEL CSRLS MODEL CSRLS Dust 68 Mod MII rev 01 SETRONIC Verona ENGLISH ...