MAIN CALIBRATION PROCEDURES
1.
E
nter menu
ž
from the main screen, press OK;
ž
enter the password, using the direction buttons
„‚ƒ
; press OK;
2.
Set up detection lines
ž
press
„
or
ƒ
until you get to < System Setup >; press OK;
ž
press
or
‚
to edit the number of the detection lines; press OK;
ž
press
or
‚
change the delay time for fault outputs; press OK;
ž
press
or
‚
change the configuration of fault outputs; press OK;
ž
press
or
‚
to set the <Com Line> configuration; press OK;
ž
press OK to skip debug function.
3.
First calibration of the detection lines (after mechanical adjustment of the
detectors)
ž
press
„
or
ƒ
until you get to < AUTO Adjust. >; press OK;
ž
press
or
‚
to change the number of the detection line to be worked on; press OK;
ž
wait until the TX value stabilises and press OK;
ž
the value of the RX must be about 100%
(see note at pag. 72)
ž
press OK to confirm the setting.
4.
Calibration of detection lines (with the barriers already previously installed)
ž
press
„
or
ƒ
until you get to < AUTO Adjust. >; press OK;
ž
press
or
‚
to change the number of the detection line to be worked on; press OK;
ž
wait until the TX value stabilises and press OK;
ž
the value of the RX must be about 100%
(see note at pag. 72)
ž
press OK to confirm the setting.
5.
Adjustment of detection line sensitivity
ž
press
„
or
ƒ
until you get to < sensitivity >; press OK;
ž
press
or
‚
to change the number of the detection line to be worked on; press OK;
ž
read the Detec value to quantify environmental disturbances;
ž
press
or
‚
to change the smoke threshold value (the value of the highest
disturbance value seen by Detec shall be less than the threshold setted) ; wait for
2 sec and press OK;
ž
read the Detec value to quantify environmental disturbances;
ž
press
to
‚
change the fire threshold value (the value of the highest
disturbance value seen by Detec shall be less than the threshold setted);
ž
wait for 2 sec and press OK to confirm the setting.
ENGLISH
Mod. MII
rev. 01
SETRONIC Verona
55
Содержание ILIA ERHSO712
Страница 1: ......
Страница 3: ...ENGLISH MANUAL ...
Страница 4: ......
Страница 6: ...HIGH SENSITIVITY LINEAR BEAM DETECTOR MODEL ERHS0712 ENGLISH 50 Mod MII rev 01 SETRONIC Verona ...
Страница 15: ...HIGH SENSITIVITY REFLECTION SYSTEM DETECTOR MODEL ERRHS0712 ENGLISH Mod MII rev 01 SETRONIC Verona 59 ...
Страница 24: ...CONTROLLER FOR BEAM DETECTOR MODEL CSRLS MODEL CSRLS Dust 68 Mod MII rev 01 SETRONIC Verona ENGLISH ...