ENGLISH
Mod. MII
rev. 01
SETRONIC Verona
63
ASSEMBLY PROCEDURE
NOTE 1:
Use the SETRONIC "Allen Key" for the opening and the closing of the detector and the
mechanical alignment of the equipment.
NOTE 2:
to grant that the socket maintain the IP65 protection degree, be sure that i twill be fixed in flat
surface. If this it is not possible use a bracket or a swivel.
1.
Fix the socket connection of the detector and carry out the wiring of the line (power supply and serial line).
2.
Set the address of the detector between 1 and 8 consequently using the Dip-Switch according to the table on page 79.
It's suggested to make these operation before the fixing of the socket.
NOTE:
The Dip-Switch 4 must be set to ON only in the last detector connected to the line open. It must
also be set with a single detector.
3.
Insert the connector plug on the bottom of the detector into the socket until you hear a "click", then lock the unit to the
socket by rotating the hooks with the appropriate Allen key and guide it to the paired device from the opposite.
4.
Repeat above operations for all the detectors are installed and the units of Reflection (Ref) omitting the part relating
to the connection line.
CONNECTIONS CHECK BEFORE START-UP
(to be made only with the loop configuration)
1.
Disconnect the two terminals "power output" and "serial line" of the main module and the two terminals "power
output" and "serial line B" of the expansion module.
2.
With a multimeter measure the resistance on the wires, between the positive output of the first power supply and
the positive of the second supply line. Also measure the resistance, always on the wires, between the negative
output of the first power supply and the negative of the second supply line.
3.
Both resistance values read, must be less than 100
Ω
4.
Reconnect the cables and make sure that the clamps are inserted securely.
CALIBRATION PROCEDURE
1.
Power the system via the controller and set the number of detectors connected and the configuration of connection
to serial line. The controller also allows the use of the two serials in an independent manner, as if they were two
separate lines open. In this case, the addresses remain the same from set 1 to 8, but you set the end of the line (Dip-
Switch 4 to ON) of both the last detector.
2.
At this point the green led of the two detector units should switch on and you must switch controller, a short flash
confirms the continuous scanning of the line. If on the units is present the condition of led flashing green and yellow
with flashes of about 2 sec., means that there is no serial communication (check the wiring for possible errors or
inversions) or incorrect configuration of the switch address. In such a case please verify: the cabling for possible
mistakes or inversions, the wrong configuration of the address switches (double same number) or the wrong
number of connected detectors (menu system set-up).
3.
Point the TRx Unit by Allen key adjustment in order to obtain the led blinking yellow.
4.
Starting i.e. from the left to move the unit slowly until the yellow led stops blinking. Then rotate the unit to the right
(the yellow led starts to flash again). Count how many turns of the key are made to obtain the yellow led off to the
opposite side. Reposition the center of movement found by dividing in half the number of revolutions counted. The
yellow led continues to blink.
5.
Do the same for the vertical axis.
6.
Point the unit of reflection following the same steps 3, 4, 5 and looking LEDs on the TRx Unit.
7.
Perform the calibration by the ground controller to follow the menu <Auto Adjust.>.
8.
Now cover the Reflection Unit with a card or opaque object. When you cover the Reflection Unit check that the
yellow led on the TRx Unit remains continuously on.
Содержание ILIA ERHSO712
Страница 1: ......
Страница 3: ...ENGLISH MANUAL ...
Страница 4: ......
Страница 6: ...HIGH SENSITIVITY LINEAR BEAM DETECTOR MODEL ERHS0712 ENGLISH 50 Mod MII rev 01 SETRONIC Verona ...
Страница 15: ...HIGH SENSITIVITY REFLECTION SYSTEM DETECTOR MODEL ERRHS0712 ENGLISH Mod MII rev 01 SETRONIC Verona 59 ...
Страница 24: ...CONTROLLER FOR BEAM DETECTOR MODEL CSRLS MODEL CSRLS Dust 68 Mod MII rev 01 SETRONIC Verona ENGLISH ...