54
Modbus
Offset
Register
Description
* System=sum of three phases
46049
6048
kVA L3
“
46050
6049
Positive Displacement PF L1
Individual Phase Positive Displacement Power Factors
(dPF); Register is 100x actual value (If the Individual
dPF (44050) is positive, this register will contain that
value else it will be zero)
46051
6050
Positive Displacement PF L2
“
46052
6051
Positive Displacement PF L3
“
46053
6052
Positive Apparent PF L1
Individual Phase Positive Apparent Power Factors
(aPF); Register is 100x actual value (If the Individual
aPF(44053) is positive, this register will contain that
value else it will be zero)
46054
6053
Positive Apparent PF L2
“
46055
6054
Positive Apparent PF L3
“
46056
6055
Amps L1
Individual Phase Instantaneous Currents (A)
46057
6056
Amps L2
“
46058
6057
Amps L3
“
46059
6058
Volts L1 to Neutral
Individual Instantaneous Phase to Neutral Voltages
(V)
46060
6059
Volts L2 to Neutral
“
46061
6060
Volts L3 to Neutral
“
46062
6061
Time Since Reset LSW (Seconds) Seconds since kWh, kVAh, kVARh and associated
Demand registers were reset. LSW (resettable)
46063
6062
Time Since Reset MSW
(Seconds)
Seconds since CAM. MSW
46080
6079
Positive kW System Average
Equals Positive KWH_SYSTEM_L&M ÷
(TimeSinceReset_L&M seconds /3600 seconds/Hr)
(resettable)
46081
6080
kW Demand System Minimum
Min Average power window (kW)