59
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47061
7060
Volts L3 to Neutral
“
47062
7061
Time Since Reset LSW (Seconds) Seconds since kWh, kVAh, kVARh and associated
Demand registers were reset. LSW (resettable)
47063
7062
Time Since Reset MSW
(Seconds)
Seconds since CAM. MSW
47080
7079
Negative kW System Average
Equals Negative KWH_SYSTEM_L&M ÷
(TimeSinceReset_L&M seconds /3600 seconds/Hr)
(resettable)
47081
7080
kW Demand System Minimum
Min Average power window (kW)
47082
7081
kVA Demand System Maximum
Maximum Instantaneous kVA Demand (kW,
resettable).
47083
7082
kVA Demand System Now
System Average kVA Demand for the most recent
(current) Demand Window (resettable).
47084
7083
kVAR Demand System Max
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.