65
Object
Identifier
Name
Description
12131
CT1 Type
1=MilliVolt, 2=Rogowski
12132
CT2 Type
1=MilliVolt, 2=Rogowski
12133
CT3 Type
1=MilliVolt, 2=Rogowski
P
ULSE
O
UTPUT
/I
NPUT
O
BJECTS
Object
Identifier
Name
Description
13020
Port 1 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed) 1 = output HIGH (open) [default]
Object 13100 present value must = 0 to use
13100
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13110
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
A
BSOLUTE
/N
ET
V
ALUE
M
EASUREMENT
O
BJECTS
System=sum of three phases.
Object
Identifier
Name
Description
* System=sum of three phases
1000
kW Demand System Maximum
System Maximum Demand (peak demand) (Unsigned/Absolute)
1010
kW Demand System Now
Average Power (kW) for most recent demand window
(Unsigned/Absolute)
1020
kW Demand System Minimum
Min Average power window (kW) (Unsigned/Absolute)