52
Modbus
Offset
Register
Description
* System=sum of three phases
46015
6014
Positive Apparent PF System
System Positive Apparent Power Factor (aPF);
Register is 100x actual value (If the System aPF
(44015) is positive, this register will contain that value
else it will be zero)
46016
6015
Amps System Avg
Average of the current in all phases.
46017
6016
Volts Line to Line Avg
Average of the system line to line voltages.
46018
6017
Volts Line to Neutral Avg
Average of the system line to neutral voltages.
46019
6018
Volts L1 to L2
Individual phase to phase voltages.
46020
6019
Volts L2 to L3
“
46021
6020
Volts L3 to L1
“
46022
6021
Measured Line Frequency
Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup,
20 point averaging array is filled with first frequency
read.
46023
6022
Positive kWh L1 LSW
Individual Phase Positive True Energy LSW (kWh,
resettable)
46024
6023
Positive kWh L1 MSW
Individual Phase Positive True Energy MSW (kWh,
resettable)
46025
6024
Positive kWh L2 LSW
“
46026
6025
Positive kWh L2 MSW
“
46027
6026
Positive kWh L3 LSW
“
46028
6027
Positive kWh L3 MSW
“