50
Modbus
Offset
Register
Description
* System=sum of three phases
44059
4058
Volts L1 to Neutral
Individual Phase to Neutral Voltages (V)
44060
4059
Volts L2 to Neutral
“
44061
4060
Volts L3 to Neutral
“
44062
4061
Time Since Reset LSW
Seconds since KWH register was reset. LSW
44063
4062
Time Since Reset MSW
Seconds since KWH register was reset. MSW
44064
4063
Data Tick Counter
Internal sample count (gets cleared every minute):
may be used to determine if sample read is a newer
sample than last read.
44080
4079
kW System Average
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M
seconds /3600 seconds/Hr) (resettable)
44081
4080
kW Demand System Min
System Minimum Demand (kW)
44082
4081
kVA Demand System Max
System Maximum Instantaneous kVA Demand (kVA,
resettable). It displays the default value after a CAM
until 1 demand window elapses. After a power cycle or
CPU reset the value is not reset but it does not update
again until 1 demand window elapses.
44083
4082
kVA Demand System Now
System Average kVA Demand For the most recent
(current) Demand Window.(resettable) Displays the
default value after a CAM or reset, or power cycle.
Updates every min thereafter. True demand value
takes a demand period to get to actual value. Similar
to 44005
44084
4083
kVAR Demand System Max
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.