Senstar LM100 calibration
Page 60
Senstar LM100 Product Guide
Defining the segments and alarm zones
When the sequencing procedure is completed, the segment setting window on the Config tab will
have one segment which is assigned to zone 1 (see
). The first segment, Segment 1,
Zone 1 includes Head: 1 to 100 (even if the system does not include 100 luminaires). Select the
Split button and there will be 2 segments, with both assigned to Zone 1. Segment 1 includes
luminaires 1 - 50 and Segment 2 includes luminaires 51 - 100. (Each time you select the split
button, you divide the selected segment into two equal sections.)
Next, specify the luminaire that will be the start point of the second segment. (e.g., If the first
segment will include luminaires 1 to 7, then the second segment will start with luminaire 8.)
Next, assign the defined segment a zone number for alarm reporting and lighting control. Each
Senstar LM100 can include up to 50 segments and up to 50 distinct alarm zones.
1.
Below the segment setting window, select the Split button.
The selected segment is divided into 2 sections, the white section is the currently selected
segment.
2.
Left-click the boundary line and drag the boundary to the appropriate point in the segment
setting window (or use the Head: field spin control to enter the number of the luminaire that
represents the start of the currently selected segment).
3.
Use the Zone: spin control to assign the segment to an alarm zone (label the zone according
to the site plan; multiple segments can be assigned to one zone).
4.
Repeat this procedure to define each luminaire segment and zone, as specified in the site
plan.
5.
Save the UCM file and download the configuration data to the gateway.
Note
Any luminaires that are used only for lighting purposes (e.g., to light a
walkway or entrance) should be assigned to a segment in which the
threshold is set to maximum (254). This enables routine scheduled
lighting control and disables alarm detection.
Note
The listed properties apply to the selected segment (Zone, Relay, Head,
Threshold, Profile).
Use the horizontal magnification button to provide a closer view.
Figure 55: Defining luminaire segments
magnification buttons
use the Delete button to merge the selected
segment with the preceding segment
segment assigned to Zone 5 has threshold set
the assigned Zone label is centered at the top
of the segment
to maximum (254) to enable scheduled light
control and disable alarm detection