Configuration settings
Intelli-FLEX II product guide • • • 7 - 7
6. When the alarm clears, the Configuration module display returns to the state
it was in before the alarm occurred, the
Zone 1
alarm LED on the processor
board goes off, the
Cut Count
and
Climb Time
are reset to their initial values,
and the Cut and Climb Windows are reset.
Climb detection testing in zone 1
1. Connect the Configuration module to the processor board.
2. Press
Display Select
as many times as necessary to light the
Zone 1,
and
Climb
LED’s.
The display shows the number of seconds of climb activity that must
accumulate before the
Climb Window
times out to initiate an alarm.
3. Attempt to climb the fence. The following events should take place:
•
the
Time Window
and
Threshold
LED’s light.
•
the display will decrease in value as climb activity accumulates until the
alarm is initiated. A climb alarm will not occur immediately. Sufficient
climb activity above the climb threshold must accumulate to cause a climb
alarm.
4. When the alarm initiates the following should occur:
•
the
Alarm
,
Zone 1
and
Climb
LED’s are lit.
•
the display shows
L1
•
the audible alarm is heard
•
on the processor board, the
Zone 1
alarm LED is lit
5. When the alarm clears, the Configuration module display returns to the state
it was in before the alarm occurred, the
Zone 1
alarm LED on the processor
board goes off, the
Cut Count
and
Climb Time
are reset to their initial values,
and the
Cut
and
Climb Windows
are reset.
Occasionally the cut alarm will occur when a climb
attempt is made. This might occur if the intruder pauses
several times during the climb attempt. This allows the
processor to decrement the cut count and may cause a
cut alarm before the climb alarm. Although each is
reported separately by the Configuration module, they
energize the same alarm relay.