UR46-81/82S
Trouble shooting
Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: e-UR46-8S_trouble_en.fm
E-45
E.
Trouble shooting
E.1
Procedure
After all adjustment, perform a check according to §
E.3
.
E.1.1
Main circuit malfunctions
Both of the following tables refer to the closing device type mounted on the circuit-breaker:
DANGER!
To ensure maximum safety, servicemen and operators must read the
A.2 "Safety
precautions"
section before starting installation, maintenance and adjustment of
the device or before starting to operate it.
Defect
Possible causes
Remedies
Over-heating
Dirty or damaged (worn or burnt)
contacts.
Clean or change the main contacts,
see §
D.7
.
Loose main conductor connections.
Tighten the connections bolts,
see §
C.12
.
Load current exceeds the circuit-
breaker admissible value.
1. Increase the power cables or
busbars cross-sections: see §
C.12
.
2. Reduce the current.
3. Change the category of circuit-
breaker.