UR46-81/82S
Technical specifications
Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: b-UR46-8S_tech data_en.fm
B-15
B.
Technical specifications
B.1
Characteristics
B.1.1
Breaking current parameters
I
ss
= Prospective sustained short circuit current
Î
ss
= Peak of I
ss
I
cut off
= Cut off current
I
d
= Setting of maximum current release
di/dt = Initial current rate of rise
U
Ne
= Rated voltage
Û
arc
= Maximum arc voltage
t
b
= Total break time
t
c
= Time-constant of the circuit
t
l
= Opening time
B.1.2
Main circuit
Refer to the corresponding data sheet for complementary information.
B.1.3
Control circuit
B.1.4
Operating conditions
Unit
UR46-81S
UR46-82S
Rated voltage
U
Ne
900 V
1800 V
Maximum operational voltage
1000 V
2000 V
Rated insulation voltage
U
Nm
3000 V
3000 V
Rated service current
I
Ne
4600 A
4600 A
Conventional free air thermal current (T
amb
=40 °C)
I
th
4600 A
4600 A
Rated short-circuit making and breaking capacity according
to EN-50123-1-2
Î
Nss
I
Nss
T
Nc
180 kA
125 kA
100 ms
115 kA
80 kA
31.5 ms
Maximum arc voltage
Û
arc
≤
2500 V
≤
4000 V
Nominal voltage
U
n
24, 36, 48, 72, 96, 110, 220 Vdc
Supply voltage limits (-25°C < T
amb
< +40°C)
0.7U
n
to 1.25U
n
03659_S
I
d
I
cut off
I
ss
0.63 I
ss
U
t
t
t
l
I
t
b
Î
ss
di/dt
Û
arc
U
Ne
t
c
Ambient outdoors temperature
T
amb
-25 °C to +40 °C
Altitude
h
≤
1400 m
Flammability
To standards NF F 16-101 - NF F 16-102 – NF ISO 1928
Содержание UR46-81S
Страница 68: ...Secheron ...